If you’re working with Allen-Bradley’s CompactLogix PLCs and PowerFlex 525 drives, integrating them over EtherNet/IP unlocks powerful advantages, like real-time status monitoring, tag-based control, and faster diagnostics.
But setting it all up correctly can be tricky if you’re new to Logix-based networks or drive profiles. This guide will walk you through the full integration process—from wiring and IP addressing to Studio 5000 configuration and test runs.
Whether you're commissioning new equipment or upgrading legacy connections, this step-by-step guide ensures a smooth and reliable setup.
Next up: we’ll assign a static IP address to the drive, confirm Ethernet connectivity, and begin the controller-side configuration.
Before your PowerFlex 525 can communicate over EtherNet/IP, it needs a static IP address. You can set this through the onboard keypad, Connected Components Workbench (CCW), or BOOTP/DHCP software.
💡 Tip: Choose an IP in the same subnet as your CompactLogix PLC. Example: If your PLC is 192.168.1.10, assign the drive something like 192.168.1.100.
ping 192.168.1.100
If ping fails, recheck cabling, subnet alignment, or firewall settings on your PC. You may also need to reboot the drive after assigning the IP.
✅ With the drive now on the network, you’re ready to integrate it into your PLC project in Studio 5000.
Once the drive is online and responding to pings, you can add it to your CompactLogix project using an Add-On Profile (AOP). This allows seamless tag-based control and status monitoring inside Logix Designer.
If this is your first time using a PF525 with Studio 5000, download the latest Add-On Profile (AOP) from Rockwell’s website. Make sure it matches the drive’s firmware version (check P053 on the drive keypad).
✅ Your drive is now part of the PLC’s I/O configuration and will generate its own tag structure automatically (e.g., PF525_Motor1:O.SpeedRef
, :I.Status
, etc.).
Once the drive is in your I/O tree and powered on, you can begin sending it commands directly from the PLC logic. Studio 5000 will automatically generate a tag set for your drive.
PF525_Motor1:I
)StatusWord
, OutputFreq
, Current
)You can now write logic to start/stop the drive, change direction, or control speed using your Output tags:
PF525_Motor1:O.Command
— Send start/stop commandsPF525_Motor1:O.SpeedRef
— Reference frequency (usually 0–4000 for 0–400.0 Hz)The AOP generates a full tag structure, including fault codes, status bits, and feedback.
DriveStatus
shows whether the drive is running, faulted, or readyFaultCode
provides active faults numerically```ladder | Start_PB Stop_PB | |----] [----+----]/[-----+-----| OTE Start_Command | | +----[ DriveStatus.OK ]----+
Once your PowerFlex 525 is online and integrated with CompactLogix, you’ll gain real-time control, fault monitoring, and easier system-wide diagnostics—all without additional analog wiring or hard I/O.
Whether you're configuring a single drive or building an entire control panel, we’re here to support you with parts, guidance, and rapid delivery.